previous

next

Defaulting the Controller

  • Defaulting the Controller completely clears the contents of the module address table
  • As the modules poll times expire, they run through their poll sync restart and re-register with the Controller which then builds the module address table again

    Because any modules that are in fault mode – such as Address out of Range or Duplicate Module – have been told to remain silent, they will not attempt to re-register with the Controller.

    The Restart All function must be used to get these modules online.

    Remember that modules in an error state that are running older firmware, remain offline until they are individually power cycled as the older firmware doesn't understand these commands.