Inputs

  • The PRT-ZX16-DIN has 16 inputs that it monitors the state of using EOL monitored or dry contact devices such as magnetic switches, PIR motion detectors and temperature thermostats. It also monitors up to 16 trouble inputs used to report trouble conditions such as module communication problems.
  • The DIN Rail Controller has 8 onboard inputs and monitors up to 64 trouble inputs. Trouble inputs will open or go in to alarm when the trouble condition is present, and close or return to normal when the trouble condition is restored. The Controller can monitor and control thousands of additional inputs and trouble inputs by using the expansion modules.
  • Devices connected to these inputs can be installed to a maximum distance of 300m (1000ft) from the ZX16 or Controller when using 22 AWG wire. Each zone input may be individually configured for normally opened and normally closed configurations with or without EOL resistors for tamper and short condition monitoring.