Set the Entry Time to 10 seconds. This will allow any users that enter the area 10 seconds to disarm it before the area generates an alarm
Set the Alternate Entry Time to 20 seconds.
This defines the entry delay time when using an alternate entry to the
area. For example, if an area can be accessed through a secondary entry
point such as a garage door, you can allow users more (or less) time to
disarm the area before an alarm is generated.
Set the Exit Time to 10 seconds. This will allow our users 10 seconds to exit the area once the arming of the area has begun before an alarm is triggered
Set the Alarm Time to 1 minute. This determines how long the bell/siren output for the area will remain activated before timing out.
Normally we would use longer Entry and Exit times, but we will keep these short for our training system.